Covering the 4.8" touchscreen below a real glass surface, the NOVOS Touch is the flagship model of the NOVOS family. With a maximum of up to 4 integrated sensors (temperature, relative humidity, CO2 and VOC) and the possibility of including external values as well, the NOVOS Touch brilliantly combines comfort and energy efficiency. Multiple design options and colors provide individualism for the most diverse applications.
Application/type | Room operating unit |
---|---|
Purpose | Room Climate Control, Lighting control, Scene control, Shading control, Measure values |
Measured values | temperature, relative humidity, absolute humidity, enthalpy, dew point, CO2, VOC, CO2/VOC mix |
Interface | Casambi (BLE), RS485 Modbus, RS485 BACnet, KNX (TP) |
Functions | temperature control, fan control, change-over, window/door monitoring, presence, lighting, blinds/shutter |
Operating functions | setpoint adjustment temperature, fan stage adjustment, presence detection, light ON/OFF/DIM, blind UP/DOWN/SET, setup scenarios, ECO function, showing measured value and history |
Operating elements | touch screen |
Configuration | NOVOSapp, App, uConfig, BUS, ETS (KNX), (depending on type) |
Input | 1x input for NTC10k or floating contact, 1x input for floating contact, 2x input for floating contact |
Network technology | RS485 Modbus, RS485 BACnet (MS/TP), KNX (TP1) |
Radio technology | 2,4 GHz, Casambi (BLE) |
Data transmission | RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) | 0..+50 |
Output signal temperature | 0..+50 °C (default setting), selectable from 4 temperature ranges -40..+60 | 0..+50 | -20..+80 | -15..+35 °C -50..+50 | 0..+50 | -20..+80 | -15..+35 °C, optionally configurable |
Operating range humidity | max. 85% rH non-condensing |
Accuracy temperature | ±0,5 K (typ. at 21 °C), within default measuring range |
Measuring range humidity | 0..100% rH non-condensing, 0..85 KJ/kg enthalpy, 0..50 | 0..80 g/m³ absolute humidity, 0..+50 | -20..+80 °C dew point, optionally configurable |
Accuracy humidity | ±2% between 10..90% rH (typ. at 21 °C) |
Measuring range CO2 | 0..2000 ppm, 0..5000 ppm, optionally configurable |
Accuracy CO2 | ±50 ppm +3% of measured value (typ. at 21 °C, 50% rH, 1015 hPa), self-calibration Dual Channel |
Measuring VOC (mixed gas) | heated metal oxide semiconductor |
Power supply | 24 V = (±10%) SELV, 24 V ~ (±10%) SELV |
Power consumption | typ. 2,5 W (24 V =), 5 VA (24 V ~) |
Display | TFT 4,8", 1120x480 px, capacitive touch technology |
Enclosure | with thermal separation and sensor channel, PC V0 |
Colour | pure white, aluminium, black |
Protection (IP) | IP30, according to EN 60529 |
Connection | tool-free mountable spring clamp, max. 1,5 mm², removable plug-in terminal, max. Ø=0,8 mm, cable entry via rear opening, predetermined breaking point (bottom) or drilling mark (top) |
Mounting | flush-mounted on standard EU box (Ø=60 mm), flush-mounted in standard EU box (Ø=60 mm, depth min. 45 mm), surface-mounted flat on base using adhesive foil or screws, base part can be mounted and wired separately |
Packaging length (mm) | 170 |
Packaging width (mm) | 110 |
Packaging height (mm) | 45 |
Packaging | case packaging |
Device length (mm) | 163 |
Device width (mm) | 106 |
Device height (mm) | 25 |
Notes | mixed gas sensors detect gases and vapours which can be oxidised (burnt): Body odours, tobacco smoke, exhalations emitted by materials (furniture, carpets, paint, glue ...) |