Application/type |
Duct averaging sensor |
Purpose |
Measure values |
Measured values |
temperature |
Interface |
LoRaWAN® (868 MHz), RS485 Modbus, RS485 BACnet, LON FT, Passive, Active, 0..5 V, 0..10 V, 4..20 mA, Switch contact |
Configuration |
USEapp, uConfig, BUS, jumper, DIP switches, LoRaWAN® Downlink, (depending on type) |
Sensor |
Pt1000 DIN cl. B, Ni1000 DIN cl. B, Ni1000TK5000, Ni891, NTC10k, NTC10k Precon, NTC20k, passive |
Output voltage |
0..10 V or 0..5 V, adjustable via jumper, live-zero configuration via app or uConfig, min. load 5 kΩ, min. load 10 kΩ |
Output current |
4..20 mA, max. load 500 Ω |
Output switch contact |
2x floating contact NO for 24 V ~ or 24 V = / 3 A |
Network technology |
RS485 Modbus, RS485 BACnet (MS/TP), LON FT (free topology) |
Radio technology |
LoRaWAN® (868 MHz) |
Data transmission |
bidirectional, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57.600, parity: none (2 stop bits), even or odd (1 stop bit) |
Operating range temperature (°C) |
-30..+70 |
Operating ranges temperature (°C) |
0..+50, -30..+70 |
Output signal temperature |
scaling analogue output, -20..+80 °C (default setting), selectable from 4 temperature ranges -50..+50 | -20..+80 | -15..+35 | -10..+120 | 0..+50 | 0..+100 | 0..+160 | 0..+250 °C, adjustable at the transducer, optionally configurable via app or uConfig |
Operating range temperature enclosure (°C) |
-30..+70, -20..+70 |
Operating range humidity |
max. 85% rH short term condensation |
Accuracy temperature |
±0,5 K (typ. at 21 °C), within default measuring range, ±0,4 K (typ. at 0 °C), ±0,2 K (typ. at 25 °C, temperature dependend), potentiometer for offset adjustment, offset setting via app or uConfig |
Power supply |
15..24 V = (±10%) SELV, 15..35 V = SELV, 24 V ~ (±10%) SELV, 19..29 V ~ SELV |
Power consumption |
typ. 0,4 W (24 V =), typ. 0,5 W (24 V =), max. 2,5 W (24 V =), 0,8 VA (24 V ~), 4,3 VA (24 V ~) |
Material in touch with media |
Sensor rod, measures the mean temperature value throughout the entire length of the sensor rod, measures the mean temperature value selectively throughout the length of the sensor rod |
Installation length (mm) |
3000, 6000 |
Display |
LCD 29x35 mm, RGB backlight, with traffic light function, threshold values configurable, optionally configurable via app or uConfig |
Enclosure |
USE-S, impact- and shock-resistant enclosure with quick-release cover, PC, USE-M, impact- and shock-resistant enclosure with quick-release cover, PC |
Colour |
pure white, transparent cover |
Protection (IP) |
IP65, according to EN 60529 |
Connection |
removable cable entry flextherm M20 for wire Ø=4,5..9 mm, removable cable entry M25 with fourfold cable entry for wire with max. Ø=7 mm, removable plug-in terminal, max. 2,5 mm², BUS max. 1,5 mm², relay max. 1,5 mm² |
Delivery content |
incl. mounting flange, incl. mounting set (screws and accessories), incl. installation set |
Packaging length (mm) |
220 |
Packaging width (mm) |
310 |
Notes |
external antenna available on request |